Aaon CC-063 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Spülung Aaon CC-063 herunter. AAON CC-063 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 52
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
CC SERIES
Condensers & Condensing Units
Installation, Operation
& Maintenance
If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
WARNING
FOR YOUR SAFETY
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
Seitenansicht 0
1 2 3 4 5 6 ... 51 52

Inhaltsverzeichnis

Seite 1 - CC SERIES

CC SERIES Condensers & Condensing Units Installation, Operation & Maintenance If the information in this manual is not fol

Seite 2

10 General Description AAON CC Series air-cooled condensers and condensing units have been designed for outdoor installation only. Startu

Seite 3 - Table of Contents

11 Direct Expansion (DX) Condensing Units Condensing units are factory assembled and wired, including a holding charge of refrigerant. Refriger

Seite 4 - Index of Tables and Figures

12 Installation AAON equipment has been designed for quick and easy installation. Locating Unit CC Series units are designed for outdoo

Seite 5

13 2-5 ton units are horizontal discharge and must have no obstruction on the discharge side of the unit. Unit should not be installed in

Seite 6

14 Route power and control wiring through the utility entries on the sides of the unit. It is recommended not to run power and control signal wires

Seite 7

15 Wire control signals to the unit’s low voltage terminal block located in the controls compartment. If any factory insta

Seite 8 - COMP TYPE

16 Determining Refrigerant Line Size The piping between the condenser and low side must ensure: 1. Minimum pressure drop, and 2. Continuo

Seite 9

17 Liquid Line Routing Care should be taken with vertical risers. When the system is shut down, gravity will pull liquid down the vertical

Seite 10 - CAUTION

18 A double suction riser can be applied to the situation of part load operation with a suction riser. A double suction riser is designe

Seite 11

19 When installing hot gas bypass risers, an oil drip line must be provided at the lowest point in the system. The oil drip line must be verti

Seite 13

20 The liquid lines have been chosen to maintain velocities between 100 and 350 fpm. The suction line diameters are selected to limit vel

Seite 14

21 Note: CC-006, CC-007, CC-008, and CC-010 HGB line sizes are based on four stage cooling operation condensing units, with two step compr

Seite 15

22 Table 3 - Predetermined Line Sizes for R-410A CC Condensing Units Model Circuit Connection Size Predetermined Line Size Liquid Suction HGB* HGR**

Seite 16

23 Startup (See back of the manual for startup form.) Compressors All compressors are equipped with crankcase heaters, whi

Seite 17

24 Units equipped with hot gas reheat must be charged with the hot gas valves closed while the unit is in cooling mode. After charging, unit should

Seite 18

25 The system is undercharged if the superheat is too high and the sub-cooling is too low. Correct an undercharged system by adding refrig

Seite 19

26 Table 5 - R-410A Refrigerant Temperature-Pressure Chart °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG 20 78.3 47 134.7 74 213.7 101 321.0 128 463.2 21

Seite 20

27 Operation Unit operations should be controlled with thermostat, or unit controller, never at the main power supply, except for emerg

Seite 21

28 Figure 4 - Variable Capacity Compressor Controller Low Voltage Terminals 24COM Module Common 24VAC Module Power C1 & C2 Demand Input P1

Seite 22

29 Figure 5 - Compressor Controller Flash Code Details Table 7 - Thermistor Temperature vs. Resistance Values °C °F kΩ °C °F kΩ -40 -40 2889.60 75 16

Seite 23

3 Table of Contents Safety ...

Seite 24

30 Low Ambient Options Adjustable fan cycling is a low ambient head pressure control option that cycles the condenser fans to maintain ref

Seite 25

31 cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be appl

Seite 26

32 use of this product, the product must be able to come in contact with the salts. These salts may be beneath any soils, grease or dirt; the

Seite 27 - Operation

33 Refrigerant Piping Diagrams Figure 6 - A/C Only Piping, AHU Above CU

Seite 28

34 Figure 7 - A/C Only Piping, AHU Below CU

Seite 29

35 Figure 8 - Modulating Hot Gas Reheat Piping, AHU Above CU

Seite 30 - Maintenance

36 Figure 9 - Modulating Hot Gas Reheat Piping, AHU Below CU

Seite 31

37 Figure 10 - Hot Gas Bypass Piping, AHU Above CU

Seite 32

38 Figure 11 - Hot Gas Bypass Piping, AHU Below CU

Seite 33 - Refrigerant Piping Diagrams

39 Figure 12 - Modulating Hot Gas Reheat with Hot Gas Bypass Piping, AHU Above CU

Seite 34

4 Index of Tables and Figures Tables: Table 1 - CC Series Clearances ...

Seite 35

40 Figure 13 - Modulating Hot Gas Reheat with Hot Gas Bypass Piping, AHU Below CU

Seite 36

41 Figure 14 - Heat Pump Piping, AHU Above CU

Seite 37

42 Figure 15 - Heat Pump Piping, AHU Below CU

Seite 38

43 Figure 16 - Heat Pump with Modulating Hot Gas Reheat Piping, AHU Above CU

Seite 39

44 Figure 17 - Heat Pump with Modulating Hot Gas Reheat, AHU Below CU

Seite 40

45 CC Series Startup Form Date:______________ Job Name:_____________________________________________________________________ Address:______________

Seite 41

46 Refrigeration System 1 - Cooling Mode Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge N/A N/A Suction N/A

Seite 42

47 Refrigeration System 1 - Heating Mode (Heat Pump Only) Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge N/A N/

Seite 43

48 Maintenance Log This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor t

Seite 44

49 Literature Change History March 2009 Update of IOM revising the model numbers, manual format, and piping diagrams to show factory installed liqui

Seite 45 - CC Series Startup Form

5 Safety Attention should be paid to the following statements:

Seite 48

AAON 203 Gum Springs Rd. Longview, TX 75602-1721 Phone: 903-236-4403 Fax: 903-236-4463 www.aaon.com CC Series Installation, Operation & M

Seite 49

6 GROUNDING REQUIRED All field installed wiring m

Seite 50

7 1. Startup and service must be performed by a Factory Trained Service Technic

Seite 51

CC Series Feature String Nomenclature Model Option : Unit Feature Options GEN MJREV UNIT SIZE VOLTAGE COMP TYPE CIRCUITS 1 2 3 4 5 6 7 CC - C -

Seite 52

CC Series Feature String Nomenclature Model Option : Unit Feature Options GEN MJREV UNIT SIZE VOLTAGE COMP TYPE CIRCUITS 1 2 3 4 5 6 7 CC - C -

Kommentare zu diesen Handbüchern

Keine Kommentare